A methodology for setting up Ggnerator out-of-step protective relays
Artículo de revista
2006-07
Universidad Autónoma de Occidente
In this article a methodology for setting up generator out-of-step protective relay, to be applied in any generator of Colombian Power System is presented. A comparison between settings proposed in research articles and a manufacturer was carried out. The application of the methodology required information as generator direct-axis transient reactance, transformer reactance, power system impedance and critical time for setting up protective relay. The proposed methodology for setting up generator out-of-step protective relay was applied in the Salvajina and Alto Anchicayá power plants, improving the selectivity with new settings approaches. En este artículo se presenta una metodología para el ajuste de la protección de pérdida de paso en generadores, que puede ser aplicada en cualquier generador del Sistema de Potencia Colombiano. Se presenta una comparación entre los criterios de ajuste propuestos en artículos de investigación y el de un fabricante. La aplicación metodológica requirió información como la reactancia transitoria de eje directo del generador, la reactancia del transformador y la impedancia del sistema, así como encontrar los tiempos críticos requeridos para un correcto ajuste de la protección. La metodología propuesta fue implementada en las protecciones de las centrales eléctricas de Salvajina y el Alto Anchicayá, mejorando la selectividad con nuevos criterios de ajuste